meta data for this page
  •  

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revisionBoth sides next revision
eigenbau:regler:pidmareike:start [2022/01/07 17:37] – [Detailed Control Options] Specified default jumper positions and clarified purposes mgangnuseigenbau:regler:pidmareike:start [2022/01/25 15:23] – [Test Protocol] default dispswitch positions mgangnus
Line 223: Line 223:
   * enable the P part by setting 2S5 to the up position. The I- and D-part remain disabled with 2S6 and 2S7 down.    * enable the P part by setting 2S5 to the up position. The I- and D-part remain disabled with 2S6 and 2S7 down. 
   * the internal control monitor signal at CONN8 should give the non-inverted signal with the same amplitude    * the internal control monitor signal at CONN8 should give the non-inverted signal with the same amplitude 
-  * disable 2S5 and enable the I-part with switch 2S6. Signal either saturates or a sinusoidal signal is arising. Use dipswitch configuration 2S1 (0000), 2S2 (0x00) to get an amplification of ca 1.+  * disable 2S5 and enable the I-part with switch 2S6. Signal either saturates or a sinusoidal signal is arising. Use dipswitch configuration 2S2 (x000), 2S1 (0000) to get an amplification of ca 1.
   * press 2S8 to check if the discharging of the integrator works. The signal should vanish for the time the button is pressed.   * press 2S8 to check if the discharging of the integrator works. The signal should vanish for the time the button is pressed.
-  * disable 2S6 and enable the D-part with switch 2S7. It should give a square-wave signal. Use dipswitch configuration 2S3 (0x00), 2S4 (0000) to get aan amplification of ca 1.+  * disable 2S6 and enable the D-part with switch 2S7. It should give a square-wave signal. Use dipswitch configuration 2S3 (0x00), 2S4 (000x) to get an amplification of ca 1.
   * Re-enable the P part fort the following tests   * Re-enable the P part fort the following tests