meta data for this page
  •  

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
eigenbau:regler:pidmareike:start [2022/01/07 17:17] – [Test Protocol] Specified jumper settings and Connectors mgangnuseigenbau:regler:pidmareike:start [2022/08/04 08:42] (current) mquensen
Line 31: Line 31:
  
 __**Connectors**__ __**Connectors**__
-| Connector  | Purpose                                 | Description                                                                                                                  | +| Connector  | Purpose                                 | Description                                                                                                                  |  
-| CONN1      | SMA signal input                        |                                                                                                                              | +| CONN1      | SMA signal input                        |                                                                                                                              |  
-| CONN2      | SUB D9 signal input                      It is supposed to be connected to a current transducer.   The pin configuration fits a LEM IT 200-S Ultrastab.              | +| CONN2      | SUB D9 signal input                      It is supposed to be connected to a current transducer.   The pin configuration fits a LEM IT 200-S Ultrastab.              |  
-| CONN3      | SMA setpoint signal                                                                                                                                                  | +| CONN3      | SMA setpoint signal                                                                                                                                                  |  
-| CONN4      | SMA monitor signal                      | gives the input signal                                                                                                       +| CONN4      | SMA monitor signal                      | gives the input signal or the input to the current transduver                                                                |  
-| CONN5      | -                                                                                                                                                                    | +| CONN5      | -                                                                                                                                                                    |  
-| CONN6      | SMA monitor internal error signal        It gives the error signal that is given to the PID controller.   The input signal is substracted from the setpoint signal. +| CONN6      | SMA monitor internal error signal        It gives the error signal that is given to the PID controller.   The input signal is substracted from the setpoint signal.  |  
-| CONN7      | JAE 5V voltage supply                   | has to be connected to the front panel's coaxial power connector                                                             | +| CONN7      | JAE 5V voltage supply                   | has to be connected to the front panel's coaxial power connector                                                             |  
-| CONN8      | SMA monitor internal control signal      gives the output of the PID part before any other operation   (e.g. filtering) is performed                                 | +| CONN8      | SMA monitor internal control signal      gives the output of the PID part before any other operation   (e.g. filtering) is performed                                 |  
-| CONN9      | SMA TTL input fast shut down            | if signal is high, controller is shut down fast                                                                              | +| CONN9      | SMA TTL input fast shut down            | if signal is high, controller is shut down fast                                                                              |  
-| CONN10     | SMA TTL input discharge integral part    if signal is high, short cuts the integral part in order to   discharge the integral capacity                               | +| CONN10     | SMA TTL input discharge integral part    if signal is high, short cuts the integral part in order to   discharge the integral capacity                               |  
-| CONN11     | SMA output signal                       | output of the controller signal                                                                                              | +| CONN11     | SMA output signal                       | output of the controller signal                                                                                              |  
-| CONN12     | SMA monitor output signal                                                                                                                                            | +| CONN12     | SMA monitor output signal                                                                                                                                            |  
-| CONN13     | SMA TTL input pick off setpoint signal  |  if signal is high, picks off the setpoint signal   and gives it to the output signal                                        | +| CONN13     | SMA TTL input pick off setpoint signal  |  if signal is high, picks off the setpoint signal   and gives it to the output signal                                        |  
-| CONN14     | JAE 5 Pin                                                                                                                                                            | +| CONN14     | JAE 5 Pin                                                                                                                                                            |  
-| CONN15     | XLR power plug                          | voltage supply                                                                                                               | +| CONN15     | XLR power plug                          | voltage supply                                                                                                               |  
 +|
  
 __**Jumper**__ __**Jumper**__
-| Jumper  | Purpose                                                                        | Description                                            | +| Jumper  | Purpose                                                                        | Description                                            |  Default Position              
-| J1      | ground connection for CONN2 housing                                            |                                                        +| J1      | ground connection for CONN2 housing                                            | solder pads                                            | open                           
-| J2      | ground connection for housing                                                  |                                                        +| J2      | ground connection for housing                                                  | solder pads                                            | open                           
-| 1J1     | sign of the setpoint input at the instrumentation amplifier at 1U1                                                                    +| 1J1     | sign of the setpoint input at the instrumentation amplifier at 1U1             pins (2x2)                                             | left to right, inverts signal  
-| 1J2     | sign of the input signal at the instrumentation amplifier at 1U3                                                                      +| 1J2     | sign of the input signal at the instrumentation amplifier at 1U3               pins (2x2)                                             | left to right, inverts signal  
-| 1J3     | sign of the current transducer signal at the instrumentation amplifier at 1U4  |                                                        +| 1J3     | sign of the current transducer signal at the instrumentation amplifier at 1U4  | pins (2x2)                                             | open                           
-| 1J4     | chooses input signal either from CONN1 or CONN2                                |                                                        +| 1J4     | chooses input signal either from CONN1 or CONN2                                | pins (3x1)                                             | middle and right pin (CONN1)   
-| 1J5     | enables/disables an input offset                                                                                                      +| 1J5     | enables/disables an input offset                                               pins (2x1)                                             | open                           
-| 3J1     | enables/disables optional low-pass filters                                                                                            +| 3J1     | enables/disables optional low-pass filters                                     pins (3x1)                                             | left and middle (disabled)     
-| 3J2     | enables/disables optional high-pass filter                                                                                            +| 3J2     | enables/disables optional high-pass filter                                     pins (3x1)                                             | left and middle (disabled)     
-| 3J3     | enables/disables an output offset                                              |                                                        +| 3J3     | enables/disables an output offset                                              | pins (2x1)                                             | closed                         
-| 3J4     | enables/disables optional ideal diode                                          |                                                        +| 3J4     | enables/disables optional ideal diode                                          | pins (3x1)                                             | left and middle (disabled)     
-| 3J5     | choose which TTL signal to use to shut down the controller                                                                            +| 3J5     | choose which TTL signal to use to shut down the controller (CONN10 or CONN9)   pins (3x1)                                             | middle and right (CONN9)       
-| 4J1     | if enabled, sets supply voltage to +12V instead of +15V                        | 4J1 and 4J2 should always be both enabled or disabled +| 4J1     | if enabled, sets supply voltage to +12V instead of +15V                        | 4J1 and 4J2 should always be both enabled or disabled  | open                           
-| 4J2     | if enabled, sets supply voltage to -12V instead of -15V                        |                                                        |+| 4J2     | if enabled, sets supply voltage to -12V instead of -15V                        | solder pads (as is 4J1)                                | open                           |
  
  
 __**Dipswitches**__ __**Dipswitches**__
  
 +<wrap hi>New: Charts of all possible settings!</wrap>
 +
 +  * For all possible settings, see: {{ :eigenbau:regler:pidmareike:first_amp_settings.pdf |1st amp}}, {{ :eigenbau:regler:pidmareike:i-part_settings.pdf |I-part}}, {{ :eigenbau:regler:pidmareike:d-part_settings.pdf |D-part}}, {{ :eigenbau:regler:pidmareike:final_amp_settings.pdf |final amp}}.
  
 **First amplification** **First amplification**
Line 203: Line 206:
  
 __**Voltage supply**__ __**Voltage supply**__
-pin+
   * supply voltage: give a supply voltage of +/-18V. Check if the voltage regulators 4U1 and 4U4 receive +/-18V and give +/-15V at pin 2.    * supply voltage: give a supply voltage of +/-18V. Check if the voltage regulators 4U1 and 4U4 receive +/-18V and give +/-15V at pin 2. 
   * reference voltage: check that 4U2 pin 6 gives +10V and 4U3 pin 6 gives -10V (which it will not do until you fix the following mistakes):   * reference voltage: check that 4U2 pin 6 gives +10V and 4U3 pin 6 gives -10V (which it will not do until you fix the following mistakes):
Line 223: Line 226:
   * enable the P part by setting 2S5 to the up position. The I- and D-part remain disabled with 2S6 and 2S7 down.    * enable the P part by setting 2S5 to the up position. The I- and D-part remain disabled with 2S6 and 2S7 down. 
   * the internal control monitor signal at CONN8 should give the non-inverted signal with the same amplitude    * the internal control monitor signal at CONN8 should give the non-inverted signal with the same amplitude 
-  * disable 2S5 and enable the I-part with switch 2S6. Signal either saturates or a sinusoidal signal is arising. Use dipswitch configuration 2S1 (0000), 2S2 (0x00) to get an amplification of ca 1.+  * disable 2S5 and enable the I-part with switch 2S6. Signal either saturates or a sinusoidal signal is arising. Use dipswitch configuration 2S2 (x000), 2S1 (0000) to get an amplification of ca 1.
   * press 2S8 to check if the discharging of the integrator works. The signal should vanish for the time the button is pressed.   * press 2S8 to check if the discharging of the integrator works. The signal should vanish for the time the button is pressed.
-  * disable 2S6 and enable the D-part with switch 2S7. It should give a square-wave signal. Use dipswitch configuration 2S3 (0x00), 2S4 (0000) to get aan amplification of ca 1.+  * disable 2S6 and enable the D-part with switch 2S7. It should give a square-wave signal. Use dipswitch configuration 2S3 (0x00), 2S4 (000x) to get an amplification of ca 1.
   * Re-enable the P part fort the following tests   * Re-enable the P part fort the following tests
  
Line 260: Line 263:
   * connect 5V supply and measure at CONN12   * connect 5V supply and measure at CONN12
   * I-part: enable the integrator at switch 2S6 and connect a TTL signal (+3.3-5V pulse) to CONN10   * I-part: enable the integrator at switch 2S6 and connect a TTL signal (+3.3-5V pulse) to CONN10
-  * when the TTL is enabled, the integrator signal should vanish (similar to the discharging butten 2S8). ASeveral seconds after the TTL is disabled, the integrator signal should reappear.+  * when the TTL is enabled, the integrator signal should vanish (similar to the discharge button 2S8). Several seconds after the TTL is disabled, the integrator signal should reappear.
   * Fast shut down: generate a control output signal with P- I- and/or D-part. Set 3J5 to connect middle and right. Connect a TTL signal to CONN9. When the TTL signal is enabled, the controller output should vanish. Several seconds after disabling the TTL signal, the output should return.   * Fast shut down: generate a control output signal with P- I- and/or D-part. Set 3J5 to connect middle and right. Connect a TTL signal to CONN9. When the TTL signal is enabled, the controller output should vanish. Several seconds after disabling the TTL signal, the output should return.
   * pickoff setpoint signal: give a setpoint signal (CONN3) that looks different to the control signal (this is usually the case when the integrator is enabled, as it smoothes out edges). Connect a TTL signal to CONN13. When the ttl signal is enabled, the controller output should give the setpoint signal. Make sure it is not the control signal that you still see (e.g. it does not change when you change control parameters in P, I and D.).    * pickoff setpoint signal: give a setpoint signal (CONN3) that looks different to the control signal (this is usually the case when the integrator is enabled, as it smoothes out edges). Connect a TTL signal to CONN13. When the ttl signal is enabled, the controller output should give the setpoint signal. Make sure it is not the control signal that you still see (e.g. it does not change when you change control parameters in P, I and D.).